Facebook pixel

How to Draw a Single Line Diagram (SLD) from Scratch

Written ByPriyanka
Published dateNov 28
Read time7 min

A single line diagram (SLD) shows a building's electrical distribution, from the incoming supply through panels and protection devices to final loads, using one line for each circuit. Think of it as the one-page story of how power travels from the DISCOM's supply point to the last light switch. It's one of the key drawings in electrical design for buildings, and this guide focuses on it.

This guide walks through SLD drawing the way you'd do it on a real job: one component at a time, for a small commercial building, with Indian codes in mind. By the end you'll know the symbols, what to show on the sheet, and a method you can repeat on your next project.

What is an SLD and why does it matter?

An SLD is a simplified electrical drawing where a single line stands in for all the conductors of a circuit, so you can see how power flows through a building without drowning in wiring. It's usually the first electrical drawing a design team makes, and every later one leans on it: load calculations, cable schedules, panel schedules, even layouts.

In India it also does a formal job. The Electrical Inspector's application for multistoried buildings, filed under Regulation 38 of the CEA Safety Regulations, 2023, asks for a single line diagram of the distribution system and the main panels, showing every device and connection with ratings and specifications.

A thin SLD slows that approval down. Contractors build panels from it, site engineers test against it, and facility teams open it ten years later to work out what feeds what, usually at an awkward hour.

An SLD is one of several MEP drawings on a project, but it's the one that sets the numbers for the rest.

SLD symbols: what do the common ones mean?

SLD symbols are standard shapes that stand for equipment. Indian drawings generally follow IEC 60617 or the Indian IS 12032 series, but always put a legend on the sheet, because clients and consultants have their own habits.

Symbol (shape)What it representsWhere it sits on the SLD
Circle with a wavy line, or a labelled boxIncoming supply (DISCOM)Top of the sheet, with voltage
Two overlapping circlesTransformerBetween HT and LT, with kVA and % impedance
Circle with GGenerator (DG set)Beside the main supply, feeding the same LT panel
Line with an X, or a box on the lineCircuit breaker (VCB, ACB, MCCB, MCB)Incomers, outgoers, sub-panel feeders
Line with a hinged bladeIsolator or switch-disconnectorWherever a section must be safely isolated
Small rectangle across the lineFuseHT metering unit, small outgoers
Thick horizontal barBusbarMain LT panel and sub-panels, with rating
Small circle(s) around the lineCurrent transformer (CT)Before meters and relays, with ratio like 400/5 A
Circle with kWhEnergy meterDISCOM metering point and sub-meters
Two short parallel linesCapacitor (APFC panel)On the LT bus, correcting power factor
Circle with MMotorPumps, AHUs, lifts
Three shrinking horizontal linesEarthNeutral, body and equipment earthing
Dashed lineFuture or proposed workSpare ways and expansion

What information must an SLD show?

A useful electrical SLD shows every piece of equipment with its rating, how it connects, and what protects it. If a number you'd need to check the design is missing, the drawing isn't finished.

  • Supply: incoming voltage (11 kV or 415 V), phases, and the metering arrangement.
  • Transformer and DG: kVA, voltage ratio, % impedance, and vector group (Dyn11 is the usual choice for distribution transformers in India).
  • Breakers and switches: type, current rating and breaking capacity in kA.
  • Busbars: current rating and short-circuit withstand.
  • Cables: runs, cores, size, conductor (Al or Cu), insulation and armouring, for example 3.5C x 185 sq.mm Al XLPE armoured. These come from your cable sizing calculation.
  • Meters, CTs and PTs: ratios and where they sit.
  • Loads: connected and demand kW for every outgoer, with a clear feeder name.
  • The basics people forget: earthing, panel tags, a legend, notes and a revision block.

Want to practise SLDs on real project drawings, not textbook sketches? Join Kaarwan's MEP course and learn design, coordination and documentation with industry mentors.


Want to practise SLDs on real project drawings, not textbook sketches? Join Kaarwan's MEP course and learn design, coordination and documentation with industry mentors.

How to draw an SLD for a small commercial building, step by step

To draw an SLD, work in the order power travels: incoming supply, transformer and DG, main LT panel, sub-panels, then final DBs and loads. Our example is a hypothetical G+3 office-and-retail building in Pune with 250 kW of connected load.

Step 0: get the numbers first. Before opening AutoCAD, have the load schedule (connected kW per floor and per system), maximum demand, the supply voltage your DISCOM will give you, and a list of loads that need backup. An SLD is only as good as the load list behind it.

Step 1: incoming supply and metering. At the top, draw the 11 kV incomer, then the HT metering unit (CT, PT, energy meter) and the HT breaker or RMU. Label the voltage and the incoming cable. Depending on your state's rules, a load this size may be supplied at 11 kV or 415 V, so confirm with the DISCOM before you draw.

Step 2: transformer and DG. Add the 11/0.433 kV transformer with kVA, % impedance and vector group. Beside it, draw the DG set and a changeover or ATS, so the grid and the DG can never feed the LT bus together.

Step 3: main LT panel. Draw a heavy busbar and label its rating. Show the transformer incomer, the DG incomer, and the outgoing feeders: floor DBs, HVAC, lifts, pumps and an APFC panel. Indian DISCOMs bill and penalise on power factor, so the capacitor bank earns its place on the sheet. Every outgoer gets a breaker rating, cable size, load in kW and a tag.

Step 4: sub-panels and floor DBs. One feeder line per floor DB, with an MCCB and cable details. Inside each DB, show the incomer and outgoing circuits (lighting, power, AC), with RCCBs on socket circuits.

Step 5: final loads and earthing. Group the final circuits, then add earthing: transformer neutral, DG neutral, body earthing and the number of earth pits. Lighting circuits come from your lighting design layout, so keep the two consistent.

Step 6: label and check. Tag everything, add the legend and notes, then trace power from the incomer to the last load. Check that breaker kA is above the fault level, cables suit their breakers, and the totals match your load schedule. Print it at A3 and read it like a stranger would.

Worked example: the finished SLD for a G+3 commercial building

Here's the finished single line diagram example, with the numbers behind it.

Single line diagram of a G+3 commercial building showing 11 kV incomer, 250 kVA transformer, 125 kVA DG set, main LT panel, sub-panels and final distribution boards.
ItemValueHow we got there
Connected load250 kWLighting and small power 60 + HVAC 120 + lifts 22 + pumps 11 + common and misc 37
Maximum demand175 kW0.7 diversity on connected load (project-specific)
Transformer250 kVA, 11/0.433 kV175 kW at 0.9 pf is 194 kVA; add 20% for growth, about 233 kVA; next standard size
LT full-load currentAbout 348 A250 kVA divided by (1.732 x 415 V)
Main incomer breaker400 ANext rating above 348 A
LT fault levelAbout 7.7 kA348 A divided by 0.045, assuming 4.5% impedance and a strong source
DG set125 kVAAbout 90 kW of essential load at 0.8 pf is 112 kVA; next standard size
DG breaker200 A125 kVA works out to about 174 A

The chain reads like this: 11 kV incomer, HT metering, VCB, 250 kVA transformer, 400 A incomer on the main LT panel (630 A busbar), with the 125 kVA DG coming in through a changeover. Out of the panel go four floor DBs, an HVAC panel, a lift panel, a pump panel and the APFC panel.

These figures are for illustration. Your diversity factors, impedance and ratings must come from your own calculations and equipment datasheets.

One more Indian detail: at 250 kW connected load, this building crosses the ECBC 2017 threshold of 100 kW connected load (or 120 kVA contract demand), so its lighting and HVAC design also have energy compliance to meet.

Draw SLDs for real projects in the MEP design course.

SLD in AutoCAD vs Revit vs ETAP: which should you use?

Use AutoCAD for the SLD you submit and issue, ETAP when the SLD has to drive studies, and Revit when panels and circuits must stay linked to a 3D model.

ToolBest forWatch out for
AutoCADA clean single line diagram in AutoCAD for approvals and tender sets, using block libraries and templatesManual: nothing updates when a load changes
RevitKeeping panels, circuits and loads tied to the building model, with panel schedules from the modelNo ready-made SLD; teams usually draft it in a drafting view or in AutoCAD
ETAPThe SLD is the model: load flow, short circuit, protection coordinationNot built for neat tender drawings, and a steeper learning curve

Starting out? Learn to draw it in AutoCAD first, because you'll understand what the other tools automate. When you're ready for the model side, see how MEP systems in Revit handle panels and circuits.

Common SLD mistakes to avoid

  • Symbols without ratings. A drawing with no kVA, amps or kA can't support a single calculation.
  • Breaker kA below the fault level. Check every breaker's breaking capacity against the fault current at its bus.
  • Missing cable details. Without size and length, voltage drop and short-circuit checks are impossible.
  • Grid and DG with no changeover. If the SLD doesn't show the interlock, it hasn't been reviewed.
  • Mixed symbol standards, no legend. Pick one standard and say which.
  • Forgetting earthing, spare ways and future expansion. Dashed lines cost nothing.
  • An SLD that doesn't match the site. Update it at as-built stage, or the next engineer inherits a fiction.

Want to be the person who prepares these drawings? This 6-month plan from site electrical engineer to electrical design engineer shows how to move into design.

FAQs

What is the difference between an SLD and a wiring diagram?

An SLD shows how a system is arranged: sources, panels, breakers, loads and their ratings, with one line per circuit. A wiring diagram shows the actual conductors, terminals and connections, wire by wire, so someone can build or troubleshoot the circuit. The SLD is the overview; the wiring diagram is the detail.

Which software is used to draw an SLD?

AutoCAD is the most common choice for submission-ready SLDs in design offices. ETAP is used when the diagram also needs load flow, short-circuit and protection studies. Revit holds panel and circuit data in a 3D model, but the SLD itself is usually drafted separately. Smaller jobs sometimes use Visio.

What should be shown on an SLD?

Show the incoming supply, transformer and DG ratings, every breaker with current rating and breaking capacity, busbar ratings, cable sizes and type, meters with CT ratios, load in kW for each outgoer, and earthing. Add a legend, panel tags and revision block. In India, Electrical Inspector submissions expect ratings and specifications on the drawing.

Who prepares the SLD in a project?

The electrical design engineer at the MEP consultant usually prepares it, based on the load calculations. The contractor's engineers may develop it further for panel manufacturing and approvals, and a licensed professional signs off where statutory approvals are needed. Site teams update it to as-built at handover.

Chat with us

Get the syllabus

View Course

Get the syllabus

View Course
curriculum-background
Phone
curriculum-background

₹3500 first call is on us 🎉

Schedule 1:1 free counselling.

  • Tailored Guidance for Your Success
  • Gain Real-World Insights
  • Life-Changing Conversation
Phone
By submitting, you agree to Kaarwan's Terms and Privacy policy

Get the syllabus

View Course

Get the syllabus

View Course
curriculum-background
Phone
curriculum-background
user-group
Not sure which skills lead to high-paying jobs?Get expert career guidance
Phone
Chat with Uswhatsapp
Priyanka

Priyanka

I’m Priyanka Choudhary, a content writer passionate about architecture, design, and turning complex ideas into clear, engaging stories.

Disclaimer: Views are the author's own and provided "as is" strictly for informational purposes. Kaarwan expressly disclaims all liability for any errors, omissions, or damages arising from this content. For corrections: hola@kaarwan.com.